Fan Coil Settings - Fan Speed Levels; Fan Coil Settings - Fan Speed Levels - Number Of Fan Speed Levels; Fan Coil Settings - Fan Speed Levels - Format Of The Level Output - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.118 Fan coil settings - Fan speed levels

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device" and the "Control value type" parameter
is set on "Fan coil".
11.5.119 Fan coil settings - Fan speed levels — Number of fan speed levels
Options:
This parameter is used to specify the number of fan speed levels the actuator will use to control
the fan of the fan coil.
11.5.120 Fan coil settings - Fan speed levels — Format of the level output
Options:
0 to 5 : The level values (0..3 or 0..5) are output in the 1-byte format as the counter values
0..3 or 0..5.
0 to 255 : The level values (0..3 or 0..5) are output as percentage values. Example 5-stage
fan: The level value 1 is output as 20%, and 5 is output as 100%.
1 Bit m from n : The level values (0..3 or 0..5) are output using 1-bit objects. The number of
objects available is the same as the number of fan speed levels. For level 2, for example,
the 1-bit fan speed level objects 1 and 2 are output as the value 1, while the other fan speed
level objects use the value 0.
1 Bit 1 from n : The level values (0..3 or 0..5) are output using 1-bit objects. The number of
objects available is the same as the number of fan speed levels. For the level 2, for
example, only the 1-bit fan speed level object 2 is output as the value 1. The other fan
speed level objects use the value 0.
Product manual 2CKA001473B9482
Description of application and parameters
3 levels
5 levels
0..5
0..255
1 bit m off n
1 bit m 1 off n
Application "Function block RTC"
│119

Advertisement

Table of Contents
loading