Object Type - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.6.7.2

Object type

Options:
1-bit switching:
The value is sent as 1-bit switching commands (0 or 1), e.g. On/Off, enabled/blocked,
true/untrue.
1-bit travel:
The value is sent as 1-bit switching commands, e.g. travel up or down.
1-bit stop/adjust:
The value is sent as 1-bit switching commands, e.g. travel stop, adjust slats.
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (percentage value).
(0 = 0%, 255 = 100%)
1 byte 0 - 255:
The value is sent as 1-byte value without a sign. Any value 0 - 255.
2-byte float:
The value is sent as floating point value (-671088.6 - 670760.9), e.g. temperature or
moisture value.
2-byte signed:
The value is sent as 2-byte value with a sign, (-32768 - +32767), e.g. time difference or
percentage difference.
2-byte unsigned:
The value is sent as 2-byte value without a sign (0 - 65535), e.g. time or brightness
value.
4-byte float:
The value is sent as 4-byte floating point value (-4000000 to 4000000), physical values,
e.g. luminosity, electric power, pressure.
4-byte signed:
The value is sent as 4-byte value with a sign (-2147483648 - 2147483647), e.g.
counting impulse, time difference.
4-byte unsigned:
The value is sent as 4-byte value without a sign (0 - 4294967295), e.g. counting
impulse.
The set option fixes the bit size of the input and output object.
Product manual 2CKA001473B9482
Description of application and parameters
1-bit switching
1-bit travel
1-bit stop/adjust
1 byte 0 - 100%
1 byte 0 - 255
2-byte float
2-byte signed
2-byte unsigned
4-byte float
4-byte signed
4-byte unsigned