Get One Alarm - 0x47
This packet returns the oldest unread entry from the alarm history. It duplicates the
functionality of packet 0x36 in a form that some masters may find more convenient. Note that
this packet causes an alarm to be marked as read in the same way as packet 36. If no unread
entries exist in the history, the response packet will contain zeros in the alarm date field.
Command packet to slave:
          Command Code (0x47) - 1 byte
Response packet from slave:
          Command Code (0x47) - 1 byte
VC4™ Date - 2 bytes
VC4™ Time - 2 bytes
          Alarm Date - 2 bytes
          Alarm Time - 2 bytes
          Gas abbreviation - 6 bytes (not null terminat'd)
          Point number - 1 byte
                    bits 0-1 point number
                    bits 2-7 undefined
          Concentration - 4 bytes (in IEEE floating point format)
          Alarm Level - 1 byte
                    bit 0: alarm level
                              0= level 1
                              1= level 2
                    bits 1-7: undefined
VC4™
153
User Manual