Honeywell VC4 User Manual page 140

4-point continuous monitor
Hide thumbs Also See for VC4:
Table of Contents

Advertisement

                    bit 5: Point Lock-ON
                              0 = No Lock-ON
                              1 = Lock-ON
                    bits 6-7: Point Locked (Ignore if bit 5 is 0.)
                              00 = Point 1
                              01 = Point 2
                              10 = Point 3
                              11 = Point 4
                    bit 8: Date Format
                              0 = MM/DD/YY
                              1 = DD/MM/YY
                    bits 9-12: Points enable when No Lock on
                              0x01 = Point 1 enabled
                              0x02 = Point 2 enabled
                              0x04 = Point 3 enabled
                              0x08 = Point 4 enabled
                    bit 13: Relay state
                              0 = De-energized
                              1 = Energized
                    bit 14: Relay Latching state
                              0 = Non-latching
                              1 = Latching
                    bit 15: Alarm Simulation state
                              0 = Unit not in alarm simulation mode
                              1 = Unit in alarm simulation mode
New Events - 1 byte
                    bit 0: The alarm history contains an entry which has not been read via packet 0x36 or
0x47.
                              1 = a new entry exists
                              0 = no new entries
                    bit 1: The fault history contains an entry which has not been read via packet 0x3D
                              1 = a new entry exists
                              0 = no new entries
VC4™
140
User Manual