1.4.4 China RoHS

1.5 Cabling

At the very minimum, all cables should include a braided shield. Ensure local electrical code
requirements are met.
Braid
Foil
Stranded
Pair
Shield
Termination
Note: Honeywell product testing uses >65% braid with foil (around the bundle); twisted pair;
stranded 24 AWG (minimum wiring for all qualification and certification testing.)
VC4™
Must have a minimum 65% coverage
When used with braid, provides 100% coverage.
Do not use foil alone. It has a tendency to break.
Provides the greatest surface area
Continuation of the shield to the cabinet earth ground is most important.
For discrete wire terminations, pigtails to the cabinet (connector) ground
should be extremely short (no greater than three inches).
For multiconductor connector terminations, only 360° shells should be
used.