Special points in DDC programming

© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Installation and Operations Guide
The property shows the execution rate of DDC in milliseconds and the number
of memory bytes DDC occupies. If DDC halts, this property returns a text string
indicating the condition that caused the halt.
Fig ure 26
The Ale rton Diagnos tic (513) prope rty s hows DDC e xe cution time
and byte s occupie d by DDC
Other properties of the Program 1024 object may be useful as well. See
"Properties of VLX/ACM-VLX Program objects" on page 93.
Branch points
Initialize
Current time
MS/TP dev cnt
|
VLX/ACM-VLX data, DDC, and automation
Used for temporary storage of values in a DDC routine.
Not available for display or as BACnet objects and
properties. Total of 128 (BR-0 through BR-127) available
when using global/building controller DDC. Total of
2048 (BR-0 through BR-2047) available when using
VisualLogic.
Flag that is ON only during the first pass of DDC. Use
Data Type 8 - Other.
Provides a count of minutes since midnight. 0 = midnight.
1339 = 11:59 p.m. Use Data Type 8 - Other.
Provides a count of the devices currently communicating
on the VLXs/ACM-VLXs MS/TP LAN.
NOTE: VLX and ACM have dedicated diagnostic
screens for MS/TP device counts. Use the Alerton/
Standard templates.