Table 2 0
EXP (ge ne ric) te chnical data
Po we r
A 24 VAC, 50-60 Hz, minimum 20 VA trans forme r is ne ce s s ary to
powe r a s ingle EXP board. Trans forme r s haring is allowe d for
powe ring multiple EXPs . Binary outputs are powe re d through
s e parate te rminals but may s hare the EXP controlle r's
trans forme r. If s hare d, the VA rating of the controlle r's trans forme r
mus t be incre as e d to account for the additional load from the
binary outputs . S e e "S ingle -point grounding" on page 25.
Fus e
Ale rto n Part Numbe r: BT-2.0A-5X20
Type : Onboard 2 Amp GDB fas t-acting fus e (5mm X 20mm)
Inputs
Jumpe r-s e le ctable , 12-bit unive rs al inputs acce pt following input
s ignals :
• The rmis tor (3K or 10K ohm) or othe r re s is tive inputs (s oftware
s calable )
• Dry contact
• 4–20 mA (no e xte rnal re s is tor re quire d)
• 0–5VDC
• 0–10 VDC
Up to 100Hz puls e inputs s upporte d ONLY on inputs 1, 2, and 3.
Binary o utputs
Binary outputs rate d 24 VAC @ 0.5 A. Each binary output has a
Hand-Off-Auto (H-O-A) s witch for manual ove rride of programme d
command. Us e one or more is olate d trans forme rs to powe r BOs
s e parate ly from the EXP board s upply powe r.
Analo g o utputs
Analog outputs are drive n by a pre cis ion D/A conve rte r and are
DIP-s witch configurable to provide e ithe r 0–10 VDC or 0–20 mA.
Each analog output has a Hand-Off-Auto s witch for manual
ove rride of programme d command. Analog outputs als o include a
pote ntiome te r for manually adjus ting the output in Hand mode .
Max. dime ns io ns
7.148" (181.56mm) H X 7.283" (181.98mm) W X 1.500"
(38.10mm) D.
Te rminatio ns
Re movable , he ade r-s tyle s cre w te rminals .
Enviro nme ntal
32–131°F (0–55°C). 0–95% RH, non-conde ns ing.
Co mmunic atio ns
Up to e ight EXPs can conne ct to a VLX/VLX-Platinum or ACM-
VLX ove r a s imple communications bus . Us e 18 AWG two
conductor twis te d s hie ld cable . Cable le ngths be twe e n
compone nts mus t not e xce e d 10ft (3.048 m).
Rating s
• Lis te d Unde rwrite rs Laboratory for Ope n Ene rgy Manage me nt
Equipme nt (PAZX) unde r the UL S tandard for S afe ty 916.
Lis ting include s both U.S . and Canadian ce rtification.
• EMC Dire ctive 89/336/EEC (Europe an CE Mark).
• FCC Part 15, S ubpart J, Clas s A.