Honeywell ALERTON ACM-VLX Installation And Operation Manual page 9

Table of Contents

Advertisement

Input configuration
jumpers for each input are
set according to input type.
IN and COM
terminals for
connecting to
universal
inputs.
SW2 for AO configuration.
Each switch corresponds to an AO.
SW1 for AXM address. Use switched 1-3 to set
AXM address in the range 0-7.
Fig ure 4
Typical AXM (I/O e xpans ion module ), AXM-1048 s hown
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Installation and Operations Guide
Status LED indicates 24VAC
and communications status.
Hand-Off-Auto (H-O-A) switches for
each output for manual override of
output status.
|
Key illustrations
Replaceable fuse.
Output LEDS indicate
operational status of
corresponding output.
24VAC power.
Maintain polarity.
AXM/EXP
communications.
Maintain polarity.
BO banks with HOT
terminals.
Trimpots for tuning AOs
from 0-100% when H-O-A
is in the H position.
AO terminals.
9