Installation and Operations Guide
IN and COM te rminals for conne ction to
unive rs al inputs . S e e page 35.
Input c o nfig uratio n jumpe rs for e ach input are
s e t according to input type . S e e page 35.
S W2 fo r AO c o nfig uratio n Each
s witch corre s ponds to an AO. S e e
page 35.
S W1 fo r EXP addre s s Us e s witche s 1-3
to s e t EXP addre s s in the range 0–7.
S e e page 30.
Fig ure 3
Typical EXP (I/O e xpans ion module ), EXP-1048 s hown
8
|
ACM-VLX/VLX/EXP/AXM
STATUS
H-O-A
EXP-1048
H-O-A
ASSEMBLED IN USA
H-O-A
H-O-A
POWER:
MAX LOAD - 68VA
H-O-A
NO BO S - 20VA
24VDC SOURCE - 250mA TOTAL
CLASS 2 CIRCUITS ONL
USE COPPER CONDUCTORS ONL
H-O-A
FOR INDOOR USE ONL
H-O-A
H-O-A
H-O-A
H-O-A
OPEN ENERG MANAGEMENT
E UIPMENT 5K05
H-O-A
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUB EC T TO THE FOLLOWING TWO CONDITIONS:
H-O-A
(1) THIS DEVICE MA NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT AN INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MA CAUSE UNDESIRED OPERATION.
S tatus LED indicate s 24VAC and
communications s tatus . S e e page 64.
Re plac e able fus e
BO 0
BO 1
BO 2
BO 3
AO 0
AO 1
AO 2
AO 3
AO 4
AO 5
AO 6
AO 7
Output LEDs indicate ope rational
s tatus of corre s ponding output.
Hand-Off-Auto (H-O-A) S witc he s for e ach output
for manual ove rride of output s tatus . S e e page 65
and page 95.
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Gro und lug for conne cting
to pane l ground. S e e
page 25.
24 VAC po we r Obs e rve
polarity. S e e page 26.
EXP c o mmunic atio ns
Obs e rve polarity. S e e
page 30 and Figure 8.
BO banks with HOT
te rminals S e e Figure 8
and page 33.
Trimpo ts for tuning AOs
from 0–100% whe n
H-O-A is in H pos ition. S e e
page 65 and page 95.
AO te rminals

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alerton acm-expAlerton acm-axm

Table of Contents