VLX/VLX-Platinum coin-cell battery replacement

Resetting the VLX and clearing data

© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
|
VLX/ACM-VLX/EXP/AXM operation and maintenance
The onboard lithium coin-cell battery provides power for the real-time clock and
for battery-backed SRAM when 24 VAC power is unavailable.
For best results, replace the coin-cell battery every three years. Standby battery
life is approximately 10 years, with 1.5 years of cumulative backup capability.
Battery life varies depending on application.
Alerton part number
Type
Always back up VLX/VLX-Platinum data to the Compass operator
CAUTIO N
workstation before replacing the coin-cell battery. It is recommended that you
replace the battery while 24 VAC power is applied to the unit. Otherwise, the
VLX/VLX-Platinum loses configuration data, and you must restore data
manually from an operator workstation.
To re plac e the VLX c o in-c e ll batte ry
1. Raise the left flap of the VLX and note the battery location.
2. Without removing power, carefully raise the battery clip about 1/8" with
a small screwdriver.
3. Dispose of the old battery in an approved method.
4. Paying attention to polarity, insert the replacement battery into the
battery clip.
5. Close the flap.
Resetting the VLX, clearing data, and clearing the ROC file may be necessary
when troubleshooting the VLX. These steps are usually performed in ascending
order. If the first does not fix the problem, try the next.
1. Reset the VLX.
2. Clear DDC and objects, and then reload them.
3. Clear ROC and reload ROC and DDC.
Procedures in this topic require operational system boot code.
IMPOR TA N T
These procedures are not effective if the SYS LED indicates a problem. In this
case, contact your Alerton dealer.
Resetting the VLX
The VLX has a Reset button, which resets CPU power without physically
removing and replacing power connections. When instructions or procedures
call for you to reset the VLX, use the Reset button.
BT-3.0V-COIN2
3.0V lithium coin cell. Duracell DL2450 or
equivalent.