Honeywell ALERTON ACM-VLX Installation And Operation Manual page 46

Table of Contents

Advertisement

Installation and Operations Guide
46
|
ACM-VLX/VLX/EXP/AXM
Table 7
Ethe rne t ne twork s e ttings
Ite m
Value
B. Ethe rne t Enable d
Y | N
C. BACne t Ove r Ethe rne t
Y | N
Enable d
D. Ne twork Numbe r
1–65,534
MS/TP network settings are items E, F, and G on the
Setting MS/TP options
Change Configuration menu.
See the BACtalk System Design Guide (LTBT-TM-SYSDSGN) for more
information about MS/TP configurations.
Use MS/TP to connect up to 10 BACnet MS/TP devices to the VLX. See Figure
6 on page 11 for more information. Do not connect the VLX to the BACnet
internetwork using MS/TP unless data traffic requirements are relatively low and
Ethernet connection is cost-prohibitive or otherwise difficult to provide. Ethernet
is the preferred primary connection method.
When connecting a VLX using MS/TP (primary connection), the total number of
devices on that MS/TP should be limited to 10 or fewer. Other factors also affect
network performance such as global-controller-hosted VLC point alarms, global
controller DDC references to devices on the MS/TP, and active operator
workstations requesting data from devices on the MS/TP.
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Re marks
S e t to Y if Ethe rne t communications is de s ire d.
De te rmine s whe the r BACne t packe ts are
trans mitte d on the Ethe rne t ne twork. Typically
s e t to Y. S e t to N only if IP is e nable d (s e e
Table 10 on page 49) and the ne twork allows
only IP packe ts . N is an advance d s e tting that
re quire s IP ne twork knowle dge and may caus e
communication failure s if us e d incorre ctly. S e e
the BACtalk S ys te m De s ign Guide (LTBT-TM-
S YS DS GN).
S e ts the BACne t ne twork numbe r for the
Ethe rne t LAN. Each inte rconne cte d BACne t
ne twork mus t have a ne twork numbe r unique
throughout the inte rne twork. S e le cting a
numbe r in the range 1–65,534 (and not 0) is
highly re comme nde d for fle xibility and future
compliance .