Table 8
MS /TP ne twork s e ttings
Ite m
Value
E. MS /TP Ne twork
1–65,534
Numbe r
F. MAC
0-127
G. Kbps
76.8, 38.4, 19.2,
15.2(ACM), 9.6
Setting EXP/AXM communications speed
bus is fixed at 76.8 Kbps. Item H on the Change Configuration menu is for
reference only.
Items for PTP connection are on a sub-menu accessed
Setting PTP options
through item O on the Change Configuration menu.
The VLX supports direct-connect using the EIA-232 port (male DB-9) on the
lower left of the VLX. The EIA-232 port supports direct connection of a
Compass operator workstation or external modem.
Table 9
PTP s e ttings
Ite m
Value
A. PTP Virtual Ne twork
1-65,534
Numbe r
B. Dire ct EIA-252 In
Y | N
Enable d
C. Dire ct EIA-252 Kbps
9.6, 38.4,
57.6, 115.2
D. Dire ct Bridge
ON | OFF
E. Dire ct s pe ake r
ON | OFF
|
Initial firmware and operator workstation setup
Re marks
S e ts the BACne t ne twork numbe r for the
MS /TP LAN. Each inte rconne cte d BACne t
ne twork mus t have a ne twork numbe r unique
throughout the ne twork. S e le cting a numbe r in
the range 1–65,534 (and not 0) is highly
re comme nde d for fle xibility and future
compliance .
S e ts the MAC addre s s of the unit on the MS /
TP LAN. Each BACne t de vice on an MS /TP
LAN mus t have a unique MAC addre s s . VLXs /
ACM-VLXs are s hippe d with a de fault MS /TP
MAC addre s s of 0.
S e ts the communication s pe e d for the MS /TP
LAN.
The EXP/AXM communications
Re marks
The virtual ne twork numbe r the VLX us e s for
PTP. Mus t be unique . No othe r ne twork can
have this ne twork numbe r on any ne twork
that will inte rconne ct. Choos e a unique
numbe r e ve n if PTP is not us e d.
S e t to Y to allow incoming conne ctions . For
e xample , s e t this to Y if you are conne cting
an e xte rnal mode m. S e tting this to N
dis able s incoming PTP data, ye t s till allows
alarm dialout.
S e ts the trans mis s ion s pe e d for EIA-232
communications . Ens ure that s e ttings on the
othe r e nd of the conne ction match.
ON allows the de vice to poll the EIA-232 line
for an e xis ting PTP conne ction, typically
us e d whe n inte grating with BACne t-
compliant e quipme nt (chille rs , boile rs , e tc.)
ove r the PTP conne ction. OFF dis able s the
VLX from polling, but doe s not dis able the
port. S e t to OFF if you are conne cting an
e xte rnal mode m.
Not us e d.
47