Honeywell EXCEL 5000 OPEN SYSTEM XFL521B Product Data

Honeywell EXCEL 5000 OPEN SYSTEM XFL521B Product Data

Distributed i/o, modules
Hide thumbs Also See for EXCEL 5000 OPEN SYSTEM XFL521B:

Advertisement

Quick Links

GENERAL
The XFL521B, 522B, 523B, and 524B modules are L
compliant digital and analog I/O modules which can be
installed at strategic locations within a building. These
modules convert sensor readings and provide output signals
used for operating actuators via L
variables (SNVTs). Each Distributed I/O module plugs into a
base terminal block allowing communication with controllers
®
via the built-in Echelon
L
ON
minal block provides spring clamp terminals for easy connec-
tion of field cables from the various sensors and actuators.
The modular system allows Distributed I/O modules to be
removed from the system without disturbing other modules.
The module with terminal block mounts easily onto a DIN-rail.
The Excel 500 CPU (XC5010C, XC5210C, XCL5010) is
capable of automatically binding and commissioning the Dis-
tributed I/O modules via the L
modules are used by other controllers, plug-ins are provided
so that the modules can be commissioned by any LNS or
non-LNS installation or network management tool.
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
ON
W
standard network
ON
ORKS
W
bus interface. The ter-
ORKS
W
bus. When the
ON
ORKS
523B, AND 524B MODULES
FEATURES
• L
M
™ compliant
ON
ARK
• 2-wire L
W
ON
ORKS
and I/O
• No additional field terminals required
• May be used with Excel 500 controllers in conjunction
with standard I/O modules
• Automatic binding and commissioning with Excel 500
• Connector module with sliding bus connector (thus
eliminating the need to wire together neighboring
modules)
• Fast connection due to spring clamp terminals
• Module exchange during operation
• Optional manual override with feedback
• Alarm in case of defective module
• Mechanical coding prevents mismatching of modules
• Power LED (L1, green) and L
(L2, red) on all electronics modules.
• Status LEDs for analog outputs and digital in- and
outputs
• Optional manual override modules for analog and
digital output modules
DESCRIPTION
M
The XFL521B, 522B, 523B, and 524B are Distributed I/O
ARK
modules that use a Neuron® chip and an FTT-10A free
topology transceiver for communication on a L
The modules are compliant with L
Guidelines V3.2.
Table 1. Modules and accessories.
Module
XFL521B
Analog Input module
XFL522B
Analog Output module
XFL523B
Digital Input module
XFL524B
Digital Output module
XSL511
L
XSL512
Manual terminal disconnect module
XSL513
Terminal block for XFL521/522/523
XSL514
Terminal block for XFL524
XFR522A
Analog Output manual override module
XFR524A
Digital Output manual override module
Distributed I/O
XFL521B, 522B,
PRODUCT DATA
®
bus interface between controller
W
ON
ORKS
M
Application Layer
ON
ARK
Description
W
connector module
ON
ORKS
EN0B-0090GE51 R1200
service LED
W
bus.
ON
ORKS

Advertisement

loading

Summary of Contents for Honeywell EXCEL 5000 OPEN SYSTEM XFL521B

  • Page 1 LNS or XSL514 Terminal block for XFL524 non-LNS installation or network management tool. XFR522A Analog Output manual override module XFR524A Digital Output manual override module ® U.S. Registered Trademark Copyright © 2000 Honeywell Inc. • All Rights Reserved EN0B-0090GE51 R1200...
  • Page 2 DISTRIBUTED I/O INTEROPERABILITY network management node commands this nci to The Distributed I/O modules are compliant to the L “CFG_EXTERNAL”, then the module will no longer modify its Application Layer Interface Guidelines, version 3.2. The Location String. This nci is stored in EEPROM and remains modules contain a L Node Object to allow monitoring there even in the event of a power failure.
  • Page 3 DISTRIBUTED I/O Table 3. Node Object network variables. NV Name Type Range Description nviRequest SNVT_obj_request RQ_NORMAL Upon receiving an update to nviRequest, nvoStatus is RQ_DISABLE updated. RQ_ENABLE RQ_UPDATE_STATUS RQ_REPOPRT_MASK RQ_SELF_TEST RQ_SELF_TEST is used only in the XFL522 analog output module for outputs configured as a motor. In this case, a synchronization is performed to set the actuator in the 0% position.
  • Page 4: Technical Data

    DISTRIBUTED I/O TECHNICAL DATA Analog Input Module XFL521B • Eight inputs (AI1 – AI8) 0 to 10 Vdc (see EN1R-1047 for impedance information) 0 to 20 mA (via external 500-ohm resistor) 4 to 20 mA (via external 500-ohm resistor) NTC 20K ohm (-50°C to +150°) PT1000 (-50°C to +150°C) •...
  • Page 5 DISTRIBUTED I/O Table 5. L Object NVs for the XFL521B. NV Name Type Range Description nvoAiValue SNVT_volt_f 0x000 (0.00 mV) to The value of the input channel connected to a 0 0x461C4000 (10V) to 10V signal after it has been filtered. Voltage is transmitted in mV.
  • Page 6 DISTRIBUTED I/O Analog Output Module XFL522B • Eight outputs (AO1 – AO8), short-circuit proof • Signal levels 0 to 10 Vdc = 11 Vdc, I = +1 mA, -1 mA • Protected outputs up to 40 Vdc / 24 Vac •...
  • Page 7 DISTRIBUTED I/O Table 6. L Object NVs for the XFL522B. NV Name Type Range Description nviValue SNVT_switch Receives the value for the output channel. nvoFeedback SNVT_switch Transmits the feedback value of the actuator output. If the manual override switch is set to 0, or if the manual override module is not plugged in, the feedback output reflects the value of nviValue.
  • Page 8 DISTRIBUTED I/O Relay Modules MCD 3 and MCE 3 FUSE The relay modules facilitate the control of peripheral devices 230 Vac / 120 Vac with high load via the analog outputs. Figure 4 and Figure 5 present connection examples for the relay modules MCD 3 and MCE 3, respectively.
  • Page 9 DISTRIBUTED I/O Digital Input Module XFL523B • Twelve inputs (DI1 – DI12) • R = 10K ohm • Max. 20 Hz input frequency • Switching conditions: OFF: U ≤ 2.5 V; ON: U ≥ 5 V • Protected switching up to 40 Vdc / 24 Vac •...
  • Page 10 DISTRIBUTED I/O Table 7. Relation between physical state and logical status as defined by the point attribute NO/NC for the XFL523B. Contact Position NO/NC Attribute Logical Status Input Voltage LED Switch On LED Switch Off ≤ 2.5 V Open Green ≥...
  • Page 11 DISTRIBUTED I/O Digital Output Module XFL524B • Six isolated change-over contacts • Max. voltage U = 230 Vac per output • Max. current I = 2 A per output • LED per channel OFF: LED off ON: LED illuminated (yellow) •...
  • Page 12 DISTRIBUTED I/O Table 10. L Object NVs for the XFL524B. NV Name Type Range Description nviValue SNVT_switch Receives the value for the output channel. nvoFeedback SNVT_switch Transmits the feedback value of the Actuator Object. If the manual override switch is set to auto, or if the manual override module is not plugged in, the feedback output reflects the value of nviValue.
  • Page 13 DISTRIBUTED I/O Terminal Block XSL513 for XFL521B/522B/523B • Mechanical coding prevents mounting of improper modules • Mounts on a DIN-rail (top-hat rail) • Spring-clamp terminals • Safety latch secures XFL module in its position The XSL513 Terminal Block has three rows of terminals: Top row: 18 signal terminals (gray);...
  • Page 14 DISTRIBUTED I/O Manual Override Module XFR522A for XFL522B (Analog Output) • Mounts on top of the XFL522B module • Potentiometer settings automatic or variable 0 – 100% • XFL 522 LEDs remain visible • Dimensions (WxLxH): 47x97x20 mm • Feedback signal including point name, status (manual, auto), and point value provided to CPU The XFR522A manual override module mounts directly on The manual override module works even if the CPU...
  • Page 15: Terminal Block Connection

    DISTRIBUTED I/O Manual Terminal Disconnect Module XSL512 • Mounts between terminal blocks and Distributed I/O modules • Manual terminal disconnect switches • 18 disconnect switches • Dimensions (WxLxH): 58x97x55 mm • Safety latch secures XFL module in its position The XSL512 Manual Terminal Disconnect module allows each of the input connections of the Terminal Block to be manually disconnected from the plugged-in module.
  • Page 16 DISTRIBUTED I/O 5. Push the sliding bus connector to the left until it locks onto the matching circuit board section on the adjacent connec- tor module (see Figure 10). 6. Lock in all other modules and connect them using the sliding bus connector.
  • Page 17 DISTRIBUTED I/O Figure 11. Clamps hold adjacent terminal blocks together. EN0B-0090...
  • Page 18 DISTRIBUTED I/O Coding the Terminal Block CAUTION Mixing the modules can destroy them. Coding the terminal block is achieved by inserting pins into designated location holes on the terminal block in the base. This codes the electronics modules to their respective terminal blocks.
  • Page 19: Setting The Module Address

    DISTRIBUTED I/O Setting the Module Address All modules will report the setting of the 16-position rotary HEX switch as a 2-byte ASCII number in the lowest 2 bytes of the Neuron® chip’s location string. Changing the rotary HEX switch setting causes the module to reset its application configuration (sensor selection, output selection, motor runtime, etc.) and go unconfigured.
  • Page 20 DISTRIBUTED I/O 1. Switch off the power to the output module or, unlock the safety latch and unplug the module from the terminal block as described in “Removing Modules and Terminal Blocks”. 2. Remove the standard cover of the module housing (XFL522A/XFL524A) as is described in "Setting the Module Address".
  • Page 21 DISTRIBUTED I/O Applying CARE Printout Labels 6. Disconnect the power to the connector module before removing the terminal block. Figure 27. Releasing the sliding bus link. Figure 24. XAL1 swivel label holder. 7. Now release the sliding bus link with a screwdriver and Normally, CARE labels can be used on electronics modules.
  • Page 22 NOTE: The cable types listed above are as recommended by Echelon® in their FTT-10A User Guide. The LOOP cable recommended by Honeywell is the level IV, 22 AWG, solid core, nonshielded cable. Belden part numbers are 9H2201504 (plenum) and 9D220150 DEVICE (non-plenum).
  • Page 23 DISTRIBUTED I/O Examples of free topology schemes (1 allowed, 2 not NOTE: In the event that the limit on the total wire length is allowed) for cable JY (St) Y 2x2x0.8 are shown below. exceeded, then FTT physical layer repeaters (FTT 10A) can be added to interconnect segments and increase the overall length by an amount equal to the original specification for that cable type and...
  • Page 24 DISTRIBUTED I/O Commissioning Distributed I/O Modules Previous to V2.04.x controller firmware, Distributed I/O An Excel 500 controller with V2.4.x firmware and modules were used only on a local L bus con- 3120E5 Neuron chip will commission earlier ver- ORKS nected to a single Excel 500 controller. Concurrent with the sions of Distributed I/O modules (XFL52x, release of V2.04.x firmware is the release of the XFL52xB XFL52xA), but only in the local mode (max 16...
  • Page 25 XI581/XI582 User Guide, EN2B-0126. When Distributed I/O modules are used exclusively by IMPORTANT: Honeywell Excel 500 controllers, it is possible to auto- It is essential that Distributed I/O modules not be matically bind their NVs to the controller. This is referred to assigned simultaneously via different MMIs.
  • Page 26: Manual Binding

    DISTRIBUTED I/O Regardless of which of these two methods is employed, Manual Binding assignment requires that the modules' rotary HEX switches There are several cases in which it is necessary to manually be set according to the CARE terminal assignment. bind the NVs of the Distributed I/O modules to their respective controller(s).
  • Page 27 Distributed I/O module. Distributed I/O module. The L service LED will ORKS Please contact Honeywell if the above actions do not solve light as long as you push the L service button. ORKS the problem.
  • Page 28 DISTRIBUTED I/O Table 16. Service LED behavior descriptions. Behavior Context Likely Explanation Power-up of the node Bad node hardware. For Distributed I/O modules, perform the tests shown in the previous section. Power-up of the node Bad node hardware. For Distributed I/O modules, perform the tests shown in the previous section.
  • Page 29 DISTRIBUTED I/O Accessories, Standards, Ratings, and Literature Accessories: Environmental Ratings: • Operating temperature: 32° to 122°F (0° to 50°C) — XAL 1 Swivel Label (required for Manual Override • Shipping/storage temperature: -13° to 150°F (-25° to Modules). 65°C) — 209541B Termination Module (one or two required, •...
  • Page 30 Figure 41. Outside dimensions of XSL513/514 terminal blocks and mounted modules in inches (mm) (side view). Home and Building Control Home and Building Control Home and Building Control Products Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17 Manufacturing P.O.