Honeywell Sylk SI06042 Product Data

Honeywell Sylk SI06042 Product Data

I/o devices

Advertisement

Sylk™ I/O Devices

APPLICATION

The Sylk IO devices are part of the Spyder family. The three
IO devices are designed to seamlessly integrate with
Spyder with relay controllers using only Sylk™ for
communication. These devices expand the footprint of a
single Spyder, increasing the controller's ability to be
applied in applications that require a large amount of
physical I/O. The Sylk IO devices are programmable using
existing Spyder wire sheets through the Niagara
Framework® software. Since the Sylk IO devices are
extensions of the Spyder LON and Spyder BACnet
controllers, the same Spyder feature will be leveraged in
the WebPro workbench tool and the WEBs-AX JACE
controller. To utilize the Sylk IO devices, the Spyder with
Relay models, PUL6438SR (for LON) or PUB6438SR (for
BACnet), need to be selected.
The Sylk IO devices are intended for use in HVAC
applications that require a programmable controller
where the IO count is more than the full sized Spyder point
count. All devices provide flexible, universal inputs for
external sensors while SIO6042 and SIO4022 provide a
combination of analog and digital outputs.

FEATURES

• Expands a single Spyder controller's IO count by 8-12
IO per device.
• Up to three devices for Lon Spyders and up to two
devices for BACnet Spyders can be applied.
• Communicates through Sylk™ bus freeing up IO for
more applications.
• Program logic resides in a single controller and uses
the existing Spyder wire sheet.
• Programming is built directly into the Spyder tool.
• Installation can be done locally or remotely.
• Field configurable and programmable for control,
input, and output functions using the Niagara
Framework® software.
• All wiring connections are made to removable
terminal blocks to simplify device installation and
replacement.
• The device housing is UL plenum rated.
Description ............................................................................................
Specifications ......................................................................................
Installation ............................................................................................
Checkout ................................................................................................
Device Replacement ........................................................................ 10
PRODUCT DATA
Contents
2
2
2
9
31-00028-02

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Sylk SI06042

  • Page 1 Sylk™ I/O Devices PRODUCT DATA APPLICATION The Sylk IO devices are part of the Spyder family. The three IO devices are designed to seamlessly integrate with Spyder with relay controllers using only Sylk™ for communication. These devices expand the footprint of a single Spyder, increasing the controller's ability to be applied in applications that require a large amount of physical I/O.
  • Page 2 SYLK™ I/O DEVICES DESCRIPTION Table 2. Universal Input Circuit Specifications. Input Sensor Operating The Sylk IO devices are available in three models, as Type Type Range described in Table 1. Room/Zone 20K Ohm -40° F to 199° F Discharge Air (-40°...
  • Page 3 SYLK™ I/O DEVICES IMPORTANT The device may be mounted in any orientation. To remove the device from the DIN rail, perform IMPORTANT the following: Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of 1.
  • Page 4 SYLK™ I/O DEVICES IMPORTANT Table 4. VA ratings for transformer sizing. • If a controller is used on Heating and Cooling Device Description Equipment (UL 1995, U.S. only) and transformer primary power is more than 150 volts, connect the PVL0000AS, Controller and Actuator transformer secondary common to earth ground PVL4022AS, and...
  • Page 5 18.9 volts reaches the Fig. 3. NEMA Class 2 transformer voltage output limits. device. This is not enough voltage for proper operation. The Honeywell transformers listed in Table 5 meet the In this situation, the engineer has three alternatives: NEMA standard DC20-1986.
  • Page 6 SYLK™ I/O DEVICES IMPORTANT WARNING If the controller and device are used on Heating and Cooling Equipment (UL 1995, U.S. only) and Electrical Shock Hazard. the transformer primary power is more than 150 Can cause severe injury, death or property volts, connect terminal 2, (the 24 Vac common [24 damage.
  • Page 7 SYLK™ I/O DEVICES NOTE: Controller and device configurations are not nec- 100 VA when powered by the same transformer essarily limited to three devices, but the total (U.S. only). For power wiring recommendations, power draw, including accessories, cannot exceed see “Power” on page 3. 2 2 2 2 2 2 2 2 3 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 2 2 2...
  • Page 8 SYLK™ I/O DEVICES — Multiple wires: up to two 18 AWG stranded, with 1/4 watt wire-wound resistor SIO4022 Prepare wiring for the terminal blocks, as follows: Terminal 1. Strip 1/2 in. (13 mm) insulation from the conductor. Label Connection 2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the required terminal location and tighten the screw.
  • Page 9 SYLK™ I/O DEVICES Table 6. Description of wiring terminal connections for Table 7. Description of wiring terminal connections for SIO12000. (Continued) SIO6042. SIO1200 SIO6042 Terminal Terminal Label Connection Label Connection UI-6 Universal Input UI-4 Universal Input UI COMMON UI-12 Universal Input UI-5 Universal Input UI COMMON...
  • Page 10 SYLK™ I/O DEVICES Step 2. Startup LED State Blink Rate Status or Condition not applicable No power to processor, LED damaged, low voltage to board, first second of power up, or 1 1 1 1 1 1 1 2 2 2 2 2 loader damaged.
  • Page 11 SYLK™ I/O DEVICES IMPORTANT Then, move to the other side of the terminal To prevent bending or breaking the alignment pins block and do the same. Repeat until the terminal on longer terminal blocks, insert the screwdriver at block is evenly raised 1/4 in. (6.35 mm) from its several points to evenly and gradually lift up the alignment pins.
  • Page 12 SYLK™ I/O DEVICES By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...

This manual is also suitable for:

Sylk si04022Sylk si012000

Table of Contents