Honeywell ALERTON ACM-VLX Installation And Operation Manual page 83

Table of Contents

Advertisement

Installation and Operations Guide
Ta bl e 2 8
Prope rtie s of VLX/ACM-VLX AV obje cts (Continue d)
Pro pe rty
W
s tatus -flags
units
priority-array
re linquis h-de fault
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Type
Example
Bit s tring
<Bit s tring>
Enume rate d
De g F
BACne t
<Array of
PriorityArray
BACnet
PriorityValue>
REAL
0
|
Appendix F: BACnet object and property reference
Re marks
A four-pos ition bit s tring that indicate s the s tatus of the
AV. If a s tatus bit =1, that s tatus is TRUE.
Indicate s the unit of me as ure , in BACne t e ngine e ring
units , for the AV pre s e nt-value .
NOT AVAILABLE IN AVs (0-7999). GENERAL
PURPOS E AVs ONLY. An array of prioritize d value s
(inde xe s 1-16) controlling the pre s e nt-value , inde x 1
having the highe s t priority. The value with the highe s t
priority controls the pre s e nt-value . Pos s ible value s for
priority-array inde xe s are re al value s or NULL. A NULL
value indicate s no command is is s ue d at that priority
inde x.
NOT AVAILABLE IN AVs (0-7999). GENERAL
PURPOS E AVs ONLY. De fault value to be us e d for
pre s e nt-value prope rty whe n all priority-array inde xe s
are NULL.