Tab le 2 7
Prope rtie s of VLX/ACM-VLX AO obje cts (Continue d)
Pro pe rty
W
out-of-s e rvice
pre s e nt-value
priority-array
re liability
re linquis h-de fault
s tatus -flags
units
Properties of VLX/ACM-VLX AV objects
Tab le 2 8
Prope rtie s of VLX/ACM-VLX AV obje cts
Pro pe rty
W
cov-incre me nt
de s cription
e ve nt-s tate
obje ct-ide ntifie r
obje ct-name
ACM
-VLX
obje ct-type
out-of-s e rvice
pre s e nt-value
82
|
ACM-VLX/VLX/EXP/AXM
Type
Example
Boole an
FALS E
REAL
75
BACne t
<Array of
PriorityArray
BACne t
PriorityValue >
BACne t_ Re liability
NO FAULT
DETECTED
REAL
0
Bit s tring
In alarm = 0,
fault = 0,
ove rridde n =
0, out of
s e rvice = 0
Enume rate d
%
Type
Example
Re al
Characte r s tring
Occupie d
S e tpoint
Enume rate d
Normal
BACne t_ Obje ct_
AV 1
Ide ntifie r
Characte r s tring
Enume rate d
AV
Boole an
FALS E
Re al
76.4
Re marks
TRUE de couple s the pre s e nt-value prope rty from the
phys ical output. While TRUE, the pre s e nt-value can be
change d to any value to s imulate conditions for te s ting
without affe cting the actual phys ical output.
Valid value s are re al numbe rs in the range 0–100.
Value s gre ate r than 100 are inte rpre te d as 100. Whe n
commande d, value s are writte n to the pre s e nt-value
with a priority for writing, which corre s ponds to a
priority-array inde x (s e e "priority-array" he re in).
An array of prioritize d value s (inde xe s 1-16) controlling
the pre s e nt-value , inde x 1 having the highe s t priority.
The value with the highe s t priority for writing controls
the pre s e nt-value . Pos s ible value s for priority-array
inde xe s are re al value s or NULL. A NULL value
indicate s no command is is s ue d at that priority le ve l.
Othe r pos s ibilitie s are OVER RANGE, UNDER
RANGE, UNRELIABLE_OTHER.
De fault value to be us e d for pre s e nt-value prope rty
whe n all priority-array inde xe s are NULL.
A four-pos ition bit s tring that indicate s the s tatus of the
obje ct. If a s tatus bit =1, that s tatus is TRUE.
Indicate s the AO's unit of me as ure in BACne t
e ngine e ring units .
Re marks
If the pre s e nt-value change s by this amount or gre ate r,
a change -of-value notification is s e nt to s ubs cribe d
de vice s . Not us e d at pre s e nt.
A de s cription as s igne d to de s cribe the obje ct's function.
This prope rty cons is ts of the obje ct-type prope rty and
the obje ct ins tance , which is a nume ric code that
ide ntifie s the obje ct of inte re s t.
For re s e rve d AVs , s hows the EXP and AV of inte re s t.
For e xample , EXP 0 AV 01/AXM 0 AV 01. Othe rwis e
s hows AV <ins tance >. The Obje ct Name prope rty is
writable whe n us ing the ACM-VLX only and not in the
VLX/VLX-Platinum.
38
Range is 3 x 10
(s ix s ignificant digits of re s olution)
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alerton acm-expAlerton acm-axm

Table of Contents