Properties of VLX/ACM-VLX BI objects
Tab le 2 9
Prope rtie s of the VLX/ACM-VLX BI obje ct
Pro pe rty
W
de s cription
e ve nt-s tate
obje ct-ide ntifie r
obje ct-name
ACM
-VLX
obje ct-type
out-of-s e rvice
polarity
pre s e nt-value
re liability
s tatus -flags
active -te xt
ACM
-VLX
inactive -te xt
ACM
-VLX
change -of-s tate -time
change -of-s tate -count
time -of-s tate -count-
re s e t
ACM
-VLX
e laps e d-active -time
time -of-active -time -
re s e t
84
|
ACM-VLX/VLX/EXP/AXM
Type
Example
Characte r s tring
Fan S tatus
Enume rate d
NORMAL
BACne t_ Obje ct_
BI 10
Ide ntifie r
Characte r s tring
EXP 7 BI 10/
AXM 7 BI 10
Enume rate d
BI
Boole an
FALS E
NORMAL
Logical s tate
ACTIVE
NO FAULT
DETECTED
Bit s tring
In alarm = 0,
fault = 0,
ove rridde n =
0, out of
s e rvice = 0
Re marks
An e ditable de s cription of the obje ct's location or
function.
This prope rty cons is ts of the Obje ct_Type prope rty and
the Obje ct Ins tance , which is a nume ric code that
ide ntifie s the obje ct of inte re s t.
The Obje ct Name prope rty is writable whe n us ing the
ACM-VLX only and not in the VLX/VLX-Platinum.
Indicate s a binary input (BI) obje ct.
TRUE de couple s the pre s e nt-value prope rty from the
phys ical input, and the pre s e nt-value doe s not track
furthe r phys ical input change s . While TRUE, the
pre s e nt-value can be change d to any value to s imulate
conditions for te s ting. FALS E indicate s that the pre s e nt-
value is tracking change s to the phys ical input.
ACTIVE or INACTIVE. Writable only whe n out-of-s e rvice
= TRUE (s e e he re in).
Othe r pos s ibility is UNRELIABLE_OTHER.
A four-pos ition bit s tring that indicate s the s tatus of the
obje ct. If a s tatus bit =1, that s tatus is TRUE.
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
Turn ON to re s e t the change -of-s tate count. Will
automatically change back to OFF.
Runtime in s e conds
Turn ON to re s e t the e laps e d-active -time prope rty. Will
automatically change back to OFF.