Honeywell ALERTON ACM-VLX Installation And Operation Manual page 35

Table of Contents

Advertisement

© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Installation and Operations Guide
Analog outputs (AOs)
AOs provide an electrical output signal in response to a software control signal
of 0–100. For EXPs/AXMs with AOs, the AO is configured with DIP switches
to provide either a current (0–20 mA) or voltage (0–10 VDC) output.
Terminal identification
Cable
Shield grounding
DIP switch settings
Universal inputs (AIs, BIs)
Universal inputs on EXPs/AXMs can accept a variety of input types. Typically, a
sensor, transducer, or other device produces an output signal that is wired to an
input terminal on the EXP/AXM. All EXP/AXM inputs are set up with jumpers.
Inputs on the EXP/AXM can be configured to accept:
• Resistance (10 K Ohm or 3 K Ohm thermistors or potentiometers)
• Voltage (0–10 VDC, 0–5 VDC)
• Current (4–20 mA)
• Dry contact
• Solid-state (transistor) switch
• Pulse-type inputs (IN-1, IN-2, and IN-3 only)
All inputs require software configuration. See "Setting up inputs" on page 53 for
details.
Terminals labeled AO n connect to the positive
side of an analog load. The immediately adjacent
COM terminal connects to the negative side.
Use 18 AWG, shielded, twisted-pair wire for all
AO connections.
Ground only the EXP/AXM side of the cable
shield to panel ground.
Do not ground both sides of the shield.
Differences in ground potential may exist from
one end to the other and cause current on the
shield.
The DIP switch bank for AO configuration is
beneath the EXPs/AXMs hinged cover doors and
labeled "AOs." DIP switch numbers correspond
directly to AO numbers. DIP 1 corresponds to
AO-0, DIP 2 to AO-1, and so on. Additional DIP
switches may be present and are unused. Set a
DIP switch to the ON position for 0–20 mA, OFF
for 0–10 VDC.
|
Hardware installation
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alerton acm-expAlerton acm-axm

Table of Contents