Properties of VLX/ACM-VLX BO objects
Ta bl e 3 0
Prope rtie s of the VLX/ACM-VLX BO obje ct
Pro pe rty
W
de s cription
e ve nt-s tate
obje ct-ide ntifie r
obje ct-name
ACM
-VLX
obje ct-type
out-of-s e rvice
pre s e nt-value
minimum-on-time
minimum-off-time
priority-array
re liability
re linquis h-de fault
s tatus -flags
active -te xt
ACM
-VLX
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Type
Example
Characte r s tring
Fan S tart/
S top
Enume rate d
Normal
BACne t_ Obje ct_
BO 1
Ide ntifie r
Characte r s tring
EXP 7 BO
01/
AXM 7 BO
01
Enume rate d
BO
Boole an
FALS E
Enume rate d
INACTIVE
Re al
60
Re al
60
BACne t
<Array of
PriorityArray
BACnet
PriorityValue>
BACne t_ Re liability
NO FAULT
DETECTED
Enume rate d
INACTIVE
Bit s tring
In alarm = 0,
fault = 0,
ove rridde n =
0, out of
s e rvice = 0
|
Appendix F: BACnet object and property reference
Re marks
An e ditable de s cription of the obje ct's location or
function.
If the obje ct doe s not s upport intrins ic re porting, the
value will be NORMAL.
This prope rty cons is ts of the obje ct-type prope rty and the
obje ct ins tance , which is a nume ric code that ide ntifie s
the obje ct of inte re s t.
The Obje ct Name prope rty is writable whe n us ing it in
the ACM-VLX only and not in the VLX/VLX-Platinum.
TRUE de couple s the pre s e nt-value prope rty from the
phys ical output. While TRUE, the pre s e nt-value can be
change d to any value to s imulate conditions for te s ting
without affe cting the actual phys ical output.
Eithe r ACTIVE or INACTIVE. Note that a NULL value
can be writte n to the pre s e nt-value on data dis plays , but
the value is actually writte n to a priority-array prope rty.
The pre s e nt-value is the re s ult of the priority array.
Enable s you to s e t anti-cycle limits for a BO in s e conds .
This is carrie d out through priority-array inde x 6. For
e xample , by writing a value of 60 to the minimum-on-
time prope rty of a BO, you s e t a minimum ON time of 60
s e conds .
Enable s you to s e t anti-cycle limits for a BO in s e conds .
This is carrie d out through priority-array inde x 6. For
e xample , by writing a value of 60 to the minimum-off-
time prope rty of a BO, you s e t a minimum OFF time of
60 s e conds .
A re ad-only array of prioritize d value s (1-16) controlling
the pre s e nt-value , priority 1 having the highe s t priority.
The value with the highe s t priority controls the pre s e nt-
value . Pos s ible value s for priority-array inde xe s are
ACTIVE, INACTIVE, or NULL. A NULL value indicate s
no command is is s ue d at that priority le ve l.
Othe r pos s ibility is UNRELIABLE_OTHER.
De fault value us e d for pre s e nt-value prope rty whe n all
priority array value s are NULL.
A four-pos ition bit s tring that indicate s the s tatus of the
obje ct. If a s tatus bit =1, that s tatus is TRUE.
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
85