ACM-VLX/VLX/EXP/AXM
For example AV-321 is the input type AV for AI-21 on EXP 0/AXM 0 (the
leading 0 is ignored when displaying the AI instance). AV-3300 is the input type
AV for AI-0 on EXP 3/AXM 3.
Table 11
Input type AVs for AI configuration
a
Re marks
AV-e 3nn Value
0
Raw c o unts
counts in the range 0–4095. An infinite ly gre at re s is tance (an ope n)
re s ults in a count of 4095. An infinite ly s mall re s is tance (a s hort)
re s ults in a count of 0.
Us e this input type AV s e tting for:
• Binary inputs (dry contacts and s witche s , e xce pt for puls e inputs )
• Any application re quiring raw counts on an input
1
S c ale d
value afte r ze ro and range s caling factors are applie d (s e e "S e tting
up input s caling" on page 54). S e e "Appe ndix B: S caling factors " on
page 75 for a re fe re nce of s caling factors for common range s .
Us e this input type AV s e tting for:
• 4–20mA inputs
• Re s is tive inputs (pote ntiome te rs )
• 0–5VDC inputs
• 0–10VDC inputs
2
3K Ohm The rmis to r (de g . F) Indicate s the input is conne cte d to
a 3K Ohm the rmis tor. No s ubs e que nt s caling or tre atme nt re quire d.
The VLX/ACM-VLX us e s an inte rnal lookup table . AI re ports
de gre e s Fahre nhe it.
3
10K Ohm The rmis to r (de g . F) Indicate s the input is conne cte d
to a 10K Ohm the rmis tor. No s ubs e que nt s caling or tre atme nt
re quire d. The VLX/ACM-VLX us e s an inte rnal lookup table . AI
re ports de gre e s Fahre nhe it.
4
Puls e
AXM inputs IN-1, IN-2, and IN-3). Indicate s the input is conne cte d
to a puls e me te r. AI-e 001, AI-e 002, or AI-e 003 as appropriate the n
re port puls e rate for the ir re s pe ctive inputs . AV-e 020, AV-e 021,
and AV-e 022 re port cons umption data. S e e "S e tting up puls e
inputs " on page 56 for more information.
5
3K Ohm The rmis to r (de g . C) Indicate s the input is conne cte d to
a 3K Ohm the rmis tor. No s ubs e que nt s caling or tre atme nt re quire d.
The VLX/ACM-VLX us e s an inte rnal lookup table . AI re ports
de gre e s Ce ntigrade .
6
10K Ohm The rmis to r (de g . C) Indicate s the input is conne cte d
to a 10K Ohm the rmis tor. No s ubs e que nt s caling or tre atme nt
re quire d. The VLX/ACM-VLX us e s an inte rnal lookup table . AI
re ports de gre e s Ce ntigrade .
a. e is the addre s s of the EXP/AXM of inte re s t (0–7) and nn is the input ide ntifie r
IN-nn, which can vary from 00–21 de pe nding on the EXP/AXM configuration.
Setting up input scaling
(Scaled), corresponding Zero and Range AVs must be set. These same values are
used for a different purpose with pulse inputs (input type AV set to 4). See
"Setting up pulse inputs" on page 56 for more information about pulse inputs.
The present-value of the AI associated with the input results from the raw count
input value (from 0–4095) affected by Zero and Range AVs.
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
De fault value . Indicate s the input will be re ad as raw
The as s ociate d AI value will re s ult from the raw input
Applie s only to AV-e 301, AV-e 302, and AV-e 303 (EXP/
When the input type AV for an input is set to 1