Honeywell MPA1 User Manual page 48

Access control unit
Table of Contents

Advertisement

1.
Select Discrete or Group and specify the available number
Default number is Discrete (single) output 1. This is the Switched Ground Door Lock
output on the MPA1
2.
Select General Settings
Configuration
Description
Name
Enter a unique name to identify the lock output
Pulse Time
configure how long a device assume to be normal status such as a
hours, minutes and seconds, Maximum time is 1:45:59
Latch
Toggle the start of the outputs between energized and de-energized
upon every activation (code use, interlock, or manual pulse)
Interlocks
Disable/ enable interlocks. See
more about Interlocks
TZ Card Toggles
Requires like the First Card Rule, a valid card read within the time
zone to enable the time zone (periods in which the doors are
unlocked) to take effect. Unlike the First Card Rule, however the user
can swipe the card a second time to return the doors to a locked
state.
Effective only if the output has a valid schedule for Energized in the
Section Scheduling. Both TZ Card Toggle and First Card Rule can
not be enable the same time
First Card Rule
First Card Rule requires a valid card read within the time zone to
enable the time zone (period in which the doors are unlocked) to take
effect.
Note
Lock Operations
Specifies the output to function in Fail Secure, or Fail Safe mode in
(default) Fail Secure mode output in normal state is not active. A lock
that needs to be powered to unlock a door will use the Fail Secure
mode. If the MPA1 is not powered the output and lock remains in it
normal state.
In Fail Safe mode the output in the normal state is activated. A lock
that needs to be Powered to lock the door (e.g a magnetic lock) will
use the Fail safe mode. If the MPA 1 is not powered the output and
lock remains in its abnormal state and releases the lock.
Note
3.
Select Scheduling
Configuration
Energized
Disable Interlocks
Effectively only if the output has a valid schedule for
Energized in the section Scheduling. Both TZ Card Toggle
and First Card Rule cant be enabled at the same time.
The MPA1 does not have the jumpers to provide Fail Safe
operation of the lock
Description
Specifies the period during which the output relay is
automatically energized (Door is unlocked), Select Schedule
(that you created in
Entering a Panel Name, page
drop down list. The Energized state of the output can be
affected by the Enabled setting for the TZ Card Toggle or First
Card Rule.
Specifies the period during which the Interlock that control
the output will be disabled, Select a Schedule (that you
created in
Entering a Panel Name, page
down list.
Configuring Interlocks, page
28) from the
28) from the drop-
Document 800-26311_ A - April 2020
| 51
63for