Master Programming Level
NAC #
1=ENABLED

2=TYPE

3=SILENCEABLE

NAC Screen #1
MS-9600 PN 51335:E1 2/14/08
3.6.5.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing
NAC Screen #1. The following screens will be displayed:
1=BELL
2=HORN
3=STROBE
1=SYNCED STROBE
2=FUTURE
3=FUTURE
1=FUTURE
2=SIREN CIRCUIT
3=BLANK
Select the NAC device type by pressing the number corresponding to the type in the
appropriate screen as shown above. When the selection is made, the display will
return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type Code
Bell
Horn
Strobe
Synced Strobe
Future
Future
Future
Siren Circuit
Blank
3.6.5.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to
Silenceable No. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each
press of the 3 key will cause the display to toggle between Silenceable Yes and
Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual
devices is programmed for silenceable and the synchronization feature is selected,
only the audible devices will be turned off if the Silence key is pressed. The visual
devices (strobes, etc.) will continue to operate.
NAC TYPE
Type Screen #1
NAC TYPE
Type Screen #2
NAC TYPE
Type Screen #3
Special Function
None
None
None
Synchronized to manufacturer
None
None
None
None
None
Programming