Master Programming Level
This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper right
corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.

Zones Disabled

Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
This display will show all of the zones that are disabled in the control panel. Note that an up and/or down arrow may appear in the upper right
corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.

Zone Type

ZONE SETUP
1=ZONE TYPES

2=ZONES AVAILABLE

Zone Setup Screen #3
This display will show the system zones (default and user programmed) and their associated types. Note that an up and/or down arrow will
appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys
to view zones Z000 through Z049.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each Zones Installed Screen. Available zone
types will be displayed in the resultant screens. For example, to change the zone type for zone Z002 in the screen illustrated above, press 3.
The following screens will be displayed:
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
To change the zone type for Z002 to Pull Station, scroll the display until Zone Type Program Screen #2 is displayed. Press 2 to program zone
Z002 as a Pull Station zone. The display will return to the Zones Installed Screen showing zone Z002 and the Pull Station program type.
Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable zone type to the selected
zone. Any signaling devices programmed to the same zone can be silenced by pressing the Alarm Silence key or by using the auto-silence fea-
ture.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 68.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central
Station.
Zones Available
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
Zone Setup Screen #3
The display will show all of the zones that are still available for programming.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Zone Types must be programmed only if a Communicator, programmed for zone reporting, is installed on the
control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a screen similar to
the following:
ZONE TYPE PROG
ZONE TYPE PROG
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
ZONES DISABLED
003
Zones Disabled Screen
ZONE TYPE PROG
1=Z000 MONITOR
2=Z001 MONITOR
3=Z002 MONITOR
Zones Installed Screen
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG
1=NONE
Zone Type Program Screen #5
ZONES AVAILABLE
001 002 003 004 005
006 007 008 009 010
011 012 013 014
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
Programming
67