Programming
See Page
62
If the selected address corresponds to a control module, a screen displaying
information about the control module with the selected address will be displayed as
shown in "Edit Module Screen for Control Modules" on page 69.
If the selected address corresponds to a monitor module, a screen displaying
information about the module with the selected address will be displayed as
illustrated in the following:
NORMAL MONITOR
EDIT MONITOR
1=ENABLED
2=TYPE
Edit Monitor Screen #2
EDIT MONITOR
1=PRE-SIGNAL
2=PAS
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR
1=ADJECTIVE/NOUN
2=DESCRIPTION
********************
Edit Monitor Screen #5
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit
Module Screen #2. Each press of the key will toggle the screen between Enabled
Yes and Enabled No. If Enabled No is selected, the module will not be polled by the
control panel, preventing the module from reporting alarms and troubles to the
panel. The control panel will indicate a system trouble condition and the Disable
LED with turn on if any devices are disabled.
<ADJ><NOUN>
ZNNN
1M012
1M012
YES
MONITOR
1M012
NO
NO
1M012
YES
1M012
Master Programming Level