Optional Modules and Devices
Primary Lines
Incoming Telco
Phone Lines
Green Wire
Tip
Red Wire
Ring
Primary Phone Line PH-1
MS-9600 PN 51335:E1 2/14/08
9. Refer to the Telephone Requirement and Warnings section of the DACT-UD
Installation and Programming Manual Document #51889, before proceeding
with this step. Connect the premises primary and secondary phone lines to the
DACT as illustrated in Figure 2.14 and test the system for correct operation
Ring
To premise phones
Tip
1 2 3 4 5 6 7 8
RJ31-X
Jack
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
7 foot cable
(MCBL-7)
order separately
Male Plug
Connectors
Female
Connectors
J3
J2
PH1
DACT-UD
Figure 2.14 Wiring Phone Jacks
Green Wire
Ring
Red Wire
Tip
1 2 3 4 5 6 7 8
RJ31-X
Jack
CAUTION: It is critical that the DACT-UD
be located as the first device on the incoming
telephone circuit to properly function
PH2
Installation
Secondary Lines
Incoming Telco
Phone Lines
Ring
To premise phones
Tip
Secondary Phone Line PH-1