Product Description

1.3 Specifications

14
AC Power - TB1
MS-9600: 120 VAC, 50/60 Hz, 3.2 amps
MS-9600E: 240 VAC, 50 Hz, 1.6 amps
Wire size: minimum 14 AWG (2.00 mm
Battery (Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Charger Capacity: 25 Amp Hour (MS-9600 cabinet holds maximum
of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 75 Amp Hour
batteries, use the CHG-75 Battery Charger and BB26 or BB-55F Battery Box. For
greater than 75 Amp Hour up to 120 Amp Hour batteries, use the CHG-120F Battery
Charger and BB-55F Battery Box).
Note: Jumper JP3, on the FACP main circuit board, must be removed to disable the
FACP battery charger when using the CHG-75 or CHG-120F.
Communication Loop - (Standard ) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft.
(900 m) untwisted, unshielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB4
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for NACs
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.5 on page 28 for information on power-limited wiring for relay
circuits
Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3,
Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mV
Up to 3.0 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Nonresettable Power #1 (24 VDC Nominal) - TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mV
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit
Nonresettable Power #2 (24 VDC Nominal) - TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mV
Total DC current available from each output is up to 3.00 amps (see Figure 1.1)
Power-limited circuit
2
) with 600 V insulation
RMS
RMS
RMS
Specifications