Honeywell Fire-Lite Alarms MS-9600 Manual page 53

Fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9600:
Table of Contents

Advertisement

Master Programming Level
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
MS-9600 PN 51335:E1 2/14/08
Type
To select the type of detector being programmed, press the 2 key while viewing the
Edit Detector Screen #2. This will cause the control panel to display the following
Detector Type Screens:
DETECTOR TYPE
1=SMOKE PHOTO
2=USER DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1
Pressing the down arrow key will display additional detector types as indicated in
the following table:
Detector Type
Smoke Photo
User-Defined-1
Smoke Ion
User-Defined-2
Heat Detect
User-Defined-3
Smoke DuctP
User-Defined-4
Superv DuctP
User-Defined-5
Future
Future
While viewing any Detector Type screen, select the type of detector being
programmed by pressing the corresponding keyboard number key. The display will
return to Edit Detector Screen #2 and indicate the selection next to the Type option.
Note: If a detector is selected as a SUPERV DUCTP type, it will function like a
supervisory point, not a fire alarm point. The supervisory LED and supervisory
relay will activate, not the fire alarm LED or alarm relay, if smoke is sensed.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm
condition and not a false alarm. This feature is selected by pressing 3 while viewing
the Edit Detector Screen #2 so that the display reads Verification On. Each time the
3 key is pressed, the display will toggle between Verification On and Verification
Off. For a detailed description, refer to "Alarm Verification" on page 122.
Walktest
The Walktest feature allows one person to test the system devices without the
necessity of manually resetting the control panel after each device activation. To
enable a device for the Walktest feature, press 1 while viewing the Edit Detector
Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause
the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on
page 122.
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel
activation (including alarm relay and communicator) for a period of 15 seconds plus
a programmable time of up to 3 minutes. Zone 97, however, will activate
immediately and may be used to connect a signaling device to indicate PAS
activation (do not use a Notification Appliance Circuit for this purpose).
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke DuctP)
Supervsory, latching
same as previous (Superv DuctP)
not used
not used
Programming
53