1.8.4 Battery Charger
1.8.4.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the
MS-9600 FACP. The FACP battery charger must be disabled when using the
CHG-75. The charger and up to 26 AH batteries can be housed in the Fire•Lite
BB-26 battery box. Larger batteries and the charger can be housed in the Fire•Lite
BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.

1.8.4.2 CHG-120F Battery Charger

The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the
MS-9600 FACP. The FACP battery charger must be disabled when using the
CHG-120F. The batteries and charger can be housed in the Fire•Lite BB-55F
battery box which can be mounted up to 20 feet away from the control panel. Note
that when using the BB-55F for housing the charger and batteries greater than
25AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for
additional information.
1.8.5 Annunciators
ACM Series LED Zone Type Annunciators
The ACM Series Annunciators remotely display alarm and trouble status as well as
system status. In addition, they can provide remote Acknowledge, Silence, Reset and
Drill functions. For more detailed information, refer to the appropriate annunciator
manual. Following is a list of annunciators which can be used with the MS-9600.
*
ACM-16ATF
Annunciator Control Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and
will accept up to three AEM-16ATF Expanders. In Canada, this module must be
used to annunciate the fire alarm input points/zones only.
AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs
*
AFM-16ATF
Annunciator Fixed Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It is fixed at address '1.' In
Canada, this module must be used to annunciate the fire alarm input points/zones
only.
*
ACM-32AF
Annunciator Control Module annunciates 32 alarm zones with 32
red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence. It has
rotary address switches and will accept one AEM-32AF Expander. In Canada,
this module must be used to annunciate the fire alarm input points/zones only.
AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32
red LEDs
*
AFM-16AF
Annunciator Fixed Module annunciates 16 alarm zones with 16 red
alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence. It is fixed
at address '1.' In Canada, this module must be used to annunciate the fire alarm
input points/zones only.
*
AFM-32AF
Annunciator Fixed Module annunciates 32 alarm zones with 32 red
LEDs. In Canada, this module must be used to annunciate the fire alarm input
points/zones only.
* In Canada, the color red must be used to indicate active alarm inputs. Yellow
indicates supervisory, burglary or trouble signals. Green indicates the presence of
power, or an activated output.