Master Programming Level
MS-9600 PN 51335:E1 2/14/08
When the last digit is keyed-in, if the selected address has not been added to
programming, a screen showing information about a device with the highest address
that is installed will be displayed.
If no detectors have been installed on the loop, the following will be displayed:
NO DETECTOR
INSTALLED
Edit Detector Screen #1
If the selected address has been added to programming, device summary screens
will be displayed. These screens allow the programmer to view all device settings
at a single glance. Pressing the left or right arrow keys will allow the programmer
to rapidly view the devices at the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not
physically installed on the SLC or has a communication fault but the address is
programmed in the system, the following screen will be displayed:
TROUBL SMOKE(PHOTO)
********************
Edit Detector Screen #1
If the selected address has been added to programming and a detector (such as a
photoelectric detector) with the selected address is physically installed on the SLC
and is communicating with the control panel, the following will be displayed:
NORMAL SMOKE (PHOTO)
*********************
Edit Detector Screen #1
To change the programming for the displayed detector, press the keyboard 'down'
arrow key to view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is
assigned to (NNN = the three digit zone number from 000 - 099)
V or * - indicates whether or not alarm verification is enabled (V = alarm
verification enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop
1, D=Detector and 017 = Detector Address 017)
ZNNN
*
1D017
ZNNN
V
1D017
Programming
51