Correlations
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP6 on the MS-9600 main circuit board to supervise placement of 4XTMF module and
circuit.
3. Cut JP5 on the MS-9600 main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 36 for detailed information.
Figure C.4 Municipal Box Connected to 4XTMF Transmitter Module
Polarities shown in alarm condition
MS-9600 PN 51335:E1 2/14/08
Figure C.4 Municipal Box Connected to 4XTMF Transmitter Module
NFPA Standard-Specific Requirements
Municipal Box
Circuit
Nonpower-limited
-
+
4XTMF
FIRE
+
-
Gamewell Model M34-
56 Local Energy
Municipal Box
153