Programming
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
52
The following examples show the editing of a photoelectric smoke detector with
address 017, located on the first SLC loop:
EDIT DETECTOR 1D017
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
EDIT DETECTOR 1D017
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
00 ** ** ** **
Edit Detector Screen #4
EDIT DETECTOR 1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Detector Screen #5
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector
Screen #2. Each press of the key will toggle the screen between Enabled Yes and
Enabled No. If Enabled No is selected, the detector will not be polled by the control
panel, preventing the detector from reporting alarms and troubles to the panel. The
control panel will display the device type and address which has been disabled and
will turn on the Trouble LED and Disable LED.