Fault And Warning Messages; Technical Data - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

446 Optional I/O extension and adapter modules
3. Set the parameters of the extension module to applicable values.
Parameter setting example for relay output
This example shows how make the relay output RO4 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
Parameter
15.07 RO4 source
15.08 RO4 ON delay
15.09 RO4 OFF delay

Fault and warning messages

Warning A7AB Extension I/O configuration failure.

Technical data

Installation
Degree of protection
Ambient conditions
Package
Reley outputs (50...52, 53...55)
Maximum wire size
Minimum contact rat-
ing
Maximum contact
rating
Maximum breaking
capacity
115/230 V inputs (70...78)
Maximum wire size
Input voltage
Maximum current
leakage in digital off
state
Isolation areas
Into an option slot on the drive control unit
IP20 / UL Type 1
See the drive technical data.
Cardboard
1.5 mm 2
12 V / 10 mA
250 V AC / 30 V DC / 2 A
1500 VA
1.5 mm 2
115 to 230 V AC ±10%
2 mA
Setting
Reverse
1 s
1 s

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents