434 Optional I/O extension and adapter modules
■
Start-up
Setting the parameters
1.
Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CAIO-01.
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of 15.02 is CAIO-01
•
set the value of parameter 15.01 to CAIO-01.
You can now see the parameters of the extension module in group 15 I/O
extension module.
3. Set the parameters of analog inputs AI3, AI4, AI5 or analog outputs AO3 or
AO4 to applicable values, see the firmware manual.
Example: To connect supervision 1 to AI3 of the extension module:
•
Select the mode of the supervision function (32.05 Supervision function 1).
•
Set limits for the supervision function (32.09 Supervision 1 low and 32.10
Supervision 1 high).
•
Select the supervision action (32.06 Supervision 1 action).
•
Connect 32.07 Supervision 1 signal to 15.52 AI3 scaled value.
CAIO-01
80 SHIELD
AI-3
AI +VE
81
AI -VE
82
83 SHIELD
AI-4
84
AI +VE
85
AI -VE
86 SHIELD
87
AI +VE
AI-5
AI -VE
88
± 11 V, ± 22 mA
SHIELD 90
AO-3
AO + 91
GND 92
SHIELD 93
AO-4
AO + 94
GND 95
0-11 V, 0-22 mA