434 Optional I/O extension and adapter modules

Start-up

Setting the parameters

1.
Power up the drive.
2. If no warning is shown,
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CAIO-01.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of 15.02 is CAIO-01
set the value of parameter 15.01 to CAIO-01.
You can now see the parameters of the extension module in group 15 I/O
extension module.
3. Set the parameters of analog inputs AI3, AI4, AI5 or analog outputs AO3 or
AO4 to applicable values, see the firmware manual.
Example: To connect supervision 1 to AI3 of the extension module:
Select the mode of the supervision function (32.05 Supervision function 1).
Set limits for the supervision function (32.09 Supervision 1 low and 32.10
Supervision 1 high).
Select the supervision action (32.06 Supervision 1 action).
Connect 32.07 Supervision 1 signal to 15.52 AI3 scaled value.
CAIO-01
80 SHIELD
AI-3
AI +VE
81
AI -VE
82
83 SHIELD
AI-4
84
AI +VE
85
AI -VE
86 SHIELD
87
AI +VE
AI-5
AI -VE
88
± 11 V, ± 22 mA
SHIELD 90
AO-3
AO + 91
GND 92
SHIELD 93
AO-4
AO + 94
GND 95
0-11 V, 0-22 mA