360 Technical data
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is
expected if the drive is used on such a network.

UL checklist

WARNING!
Operation of this drive requires detailed installation and operation
instructions provided in the hardware and software manuals. The manuals
are provided in electronic format in the drive package or on the Internet.
Keep the manuals with the drive at all times. Hard copies of the manuals can
be ordered through the manufacturer.
Make sure that the drive type designation label includes the applicable marking.
DANGER - Risk of electric shock. After disconnecting the input power, always
wait for 5 minutes to let the intermediate circuit capacitors discharge before
you start working on the drive, motor or motor cable.
The drive is to be used in a heated, indoor controlled environment. The drive
must be installed in clean air according to the enclosure classification. Cooling
air must be clean, free from corrosive materials and electrically conductive
dust.
For IP66 (UL Type 4X drives): The drive can be used outdoors if protected from
the heat of the sun and indoors or outdoors in a dusty environment. The surface
has been tested against exposure to corrosive agents such as salt spray,
cleaners containing ammonia and chlorine, algaecides and microbicides.
The maximum surrounding air temperature is 40 °C at rated output current.
The output current is derated for 40...50 °C.
The drive is suitable for use in a circuit capable of delivering not more than
100 kA rms symmetrical amperes, 600 V maximum when protected by the UL
fuses given elsewhere in this chapter.
The drive is suitable for use in a circuit capable of delivering not more than
65 kA rms symmetrical amperes, 600 V maximum when protected by the UL
circuit breakers given elsewhere in this chapter.
The cables located within the motor circuit must be rated for at least 75 °C in
UL-compliant installations.
The input cable must be protected with fuses or circuit breakers. These
protective devices provide branch circuit protection in accordance with the
national regulations (National Electrical Code (NEC) or Canadian Electrical
Code). Obey also any other applicable local or provincial codes.