Connecting The Power Cables; Connection Diagram - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

Connecting the power cables

Connection diagram

L1
PE
1
2
(PE)
PE
(PE)
L1
1
Two protective earth (ground) conductors. Drive safety standard IEC/EN/UL 61800-
5-1 requires two PE conductors if the cross-sectional area of the PE conductor is less
than 10 mm 2 Cu or 16 mm 2 Al. For example, you can use the cable shield in addition to
the fourth conductor.
2
Use a separate grounding cable or a cable with a separate PE conductor for the line
side if the conductivity of the fourth conductor or shield does not meet the requirements
for the PE conductor.
3
Use a separate grounding cable for the motor side if the conductivity of the shield is
not sufficient, or if there is no symmetrically constructed PE conductor in the cable.
4
360-degree grounding of the cable shield is required for the motor cable and brake
resistor cable (if used). It is also recommended for the input power cable.
5
If necessary, install an external filter (d u /d t , common mode, or sine filter). Filters are
available from ABB.
6
For IP66 (UL Type 4X) drive with optional disconnect, wire to terminals 2T1, 4T2 and
6T3. External disconnect is not needed but external fuses are still required.
L2
L3
4
6
L2
L3
Electrical installation – Global (IEC) 139
R+
R-
T1/U T2/V T3/W
UDC+
4
5
U1
3
V1
W1
PE
M
3