126 Guidelines for planning the electrical installation
2. If there is basic insulation between the sensor and the live parts of the motor,
or if the insulation type is not known: You can connect the sensor to the drive
via an option module. The sensor and the module must form a double or
reinforced insulation between the motor live parts and the drive control unit.
See
Connecting a motor temperature sensor to the drive through an option
module (page
allowed voltage over the sensor.
3. If there is basic insulation between the sensor and the live parts of the motor,
or if the insulation type is not known: You can connect a sensor to a digital
input of the drive via an external relay. The sensor and the relay must form a
double or reinforced insulation between the motor's live parts and the digital
input of the drive. Make sure that the voltage does not exceed the maximum
allowed voltage over the sensor.
Connecting a motor temperature sensor to the drive through an option
module
This table shows:
option module types that you can use for the motor temperature sensor
connection
insulation or isolation level that each option module forms between its
temperature sensor connector and other connectors
temperature sensor types that you can connect to each option module
temperature sensor insulation requirement in order to form, together with
the insulation of the option module, a reinforced insulation between the motor
live parts and the drive control unit.
Option module
Type
Insulation/Isolation
CMOD-
Reinforced insulation between
02
the sensor connector and other
connectors (including drive
CPTC-02
control unit connector).
The drive control unit is PELV
compatible also when the mod-
ule and a thermistor protection
circuit are installed.
For more information, refer to
Connecting motor temperature sensors to the drive (page 224)
126). Make sure that the voltage does not exceed the maximum
Temperature sensor
type
PTC
KTY
Pt100,
Pt1000
x
-
-
x
-
-
Temperature sensor
insulation require-
ment
No special require-
ment
No special require-
ment