Diagnostics

LEDs

The adapter module has one diagnostic LED.
Color
Green

Technical data

Installation
Degree of protection
Ambient conditions
Package
Analog inputs (80...82, 83...85)
Maximum wire size
Input voltage (AI+ and
AI-)
Input resistance
Optional cable shield connection
Analog outputs (86...88, 89...91)
Maximum wire size
Output voltage (AO+
and AGND)
Output resistance
Recommended load
Inaccuracy
Optional cable shield connection
Analog output scale switch
ON state
OFF state
Isolation areas
Optional I/O extension and adapter modules 441
Into SLOT 2 on the drive control unit
IP20
See the drive technical data.
Cardboard
1.5 mm 2
-10 V ... +10 V
> 200 kohm
1.5 mm 2
0 V ... +10 V
< 20 ohm
> 10 kohm
typical ±1%, max. ±1.5% of full scale
0.5 V ... 9.5 V range in use
0 V ...10 V range in use
Description
The adapter module is powered up.