Gg Fuses - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

it operates rapidly enough. The operating time depends on the supply network
impedance and the cross-sectional area and length of the supply cable.
Note 1: See also
Implementing short-circuit and thermal overload
protection (page
Note 2: Fuses with higher current rating than the recommended ones must not
be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and
the melting curve of the fuse does not exceed the melting curve of the fuse
mentioned in the table.

gG fuses

Check on the fuse time-current curve to ensure the operating time of the fuse is
below 0.5 seconds. Obey the local regulations.
ACS580-
Min.
01-...
short-
circuit
1)
current
A
3-phase U n = 230 V
04A7-2
200
06A7-2
200
07A6-2
200
012A-2
200
018A-2
200
025A-2
320
032A-2
320
047A-2
500
060A-2
500
089A-2
1300
091A-2
1300
115A-2
1300
144A-2
1700
171A-2
2300
213A-2
3300
248A-2
-
117).
Input
current
Nominal
current
A
A
4.7
25
6.7
25
7.6
25
12.0
25
16.9
25
24.5
40
31.2
40
46.7
63
60
63
89
125
91
125
115
125
144
200
171
250
213
315
273
-
gG (IEC 60269)
I 2 t
Voltage
rating
A 2 s
V
2500
500
2500
500
2500
500
2500
500
2500
500
7700
500
7700
500
20100
500
20100
500
103000
500
103000
500
103000
500
300000
500
600000
500
710000
500
-
-
Technical data 291
ABB type
IEC
60269
size
OFAF000H25
000
OFAF000H25
000
OFAF000H25
000
OFAF000H25
000
OFAF000H25
000
OFAF000H40
000
OFAF000H40
000
OFAF000H63
000
OFAF000H63
000
OFAF00H125
00
OFAF00H125
00
OFAF00H125
00
OFAF0H200
0
OFAF0H250
0
OFAF1H315
1
-
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents