Internal +24 V power supply
PNP connection (source)
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.
NPN configuration for digital inputs (X2 & X3)
Internal and external +24 V power supply connections for NPN configuration are
shown in the figure below.
Internal +24 V power supply
NPN connection (sink)
Note: DI6 is not supported in the NPN configuration.
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.
Connection for obtaining 0...10 V from analog output 2 (AO2)
To obtain 0...10 V from analog output AO2, connect a 500 ohm resistor (or two
1 kohm resistors in parallel) between analog output AO2 and analog common
ground AGND.
X2 & X3
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
X2 & X3
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
Control unit 225
External +24 V power supply
PNP connection (source)
X2 & X3
10
0 V DC
11
+24 V DC
12
13
14
15
16
17
18
External +24 V power supply
NPN connection (sink)
X2 & X3
10
11
+24 V DC
12
0 V DC
13
14
15
16
17
18
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6