Typical Power Cables Ul (Nec) - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

338 Technical data
ACS580-01-...
12A7-4
018A-4
026A-4
033A-4
039A-4
046A-4
062A-4
073A-4
088A-4
089A-4
106A-4
145A-4
169A-4
206A-4
246A-4
293A-4
363A-4
430A-4
1) The cable sizing is based on max. 6 cables laid on a cable ladder side by side, ambient temperature 30
°C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364- 5-52/2001). For other
conditions, size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive. See page
2) Aluminum cables can be used with U n = 230 V frames R5...R8 only.

Typical power cables UL (NEC)

ACS580-01-...
3-phase U 1 = 200...240 V, P n at U n = 208/230 V, 60 Hz
04A6-2
06A6-2
07A5-2
10A6-2
Frame size
R1
R2
R2
R3
R3
R3
R4, R4 v2
R4, R4 v2
R5
R4 v2
R5
R6
R7
R7
R8
R8
R9
R9
330
for the accepted cable sizes of the drive.
Frame size
R1
R1
R1
R1
1)
Cu cable type
mm 2
3×2.5 + 2.5
3×2.5 + 2.5
3×6 + 6
3×10 + 10
3×10 + 10
3×10 + 10
3×25 + 16
3×35 + 16
3×50 + 25
3×50 + 25
3×70 + 35
3×95 + 50
3×120 + 70
3×150 + 70
2×(3×70+35)
2×(3×95+50)
2×(3×120+70)
2×(3×150+70)
1)
2)
AI cable type
,
mm 2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Cu cable type
AWG/kcmil
14
14
14
14