228 Control unit

Technical data

R1...R5
External power supply
through option module
CMOD-01 or CMOD-02
+24 V DC output
(Term. 10)
Digital inputs DI1...DI6
(Term. 13...18)
Relay outputs RO1...RO3
(Term. 19...27)
Maximum power: 25 W, 1.04 A at 24 V AC/DC ±10% as standard
Terminal size: 0.2 ... 2.5 mm 2 (24 ... 14 AWG)
Total load capacity of this outputs is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on
board.
Terminal size: 0.2 ... 2.5 mm 2 (24 ... 14 AWG)
Input type: NPN/PNP
Terminal size: 0.14 ... 1.5 mm 2 (26 ... 16 AWG)
DI1...DI4 (Term. 13...16)
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
R in : 3 kohm
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
DI5 (Term.17)
Can be used as a digital or frequency input.
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
R in : 3 kohm
Max. frequency: 16 kHz
Symmetrical signal (duty cycle D = 0.50)
DI6 (Term.18)
Can be used as a digital or PTC input.
12/24 V DC logic levels: "0" < 3 V, "1" > 8 V
R in : 3 kohm
Max. frequency: 16 kHz
Symmetrical signal (duty cycle D = 0.50)
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
Note: DI6 is not supported in the NPN configuration.
PTC mode – PTC thermistor can be connected between DI6 and
+24 V DC: < 1.5 kohm = '1' (low temperature), > 4 kohm = '0'
(high temperature), open circuit = '0' (high temperature).
DI6 is not a reinforced/double insulated input. Connecting the
motor PTC sensor to this input requires usage of a rein-
forced/double insulated PTC sensor inside the motor
250 V AC / 30 V DC, 2 A. Terminal size: 0.14 ... 1.5 mm 2 (26 ... 16
AWG)