Ul (Nec) - Ip21 And Ip55 (Ul Type 1 And 12) - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

ACS580-01-...
05A7-4+B063
07A3-4+B063
09A5-4+B063
12A7-4+B063
018A-4+B063
026A-4+B063
033A-4+B063
039A-4+B063
046A-4+B063
1) When disconnect option is included, add 5 W (17 BTU/h) for R1 and R2; add 12 W for R3 (41 BTU/h)

UL (NEC) - IP21 and IP55 (UL Type 1 and 12)

ACS580-
Typical heat dissipa-
01-...
3-phase U 1 = 200...240 V, P n at U n = 208/230 V, 60 Hz
04A6-2
50
06A6-2
69
07A5-2
79
10A6-2
120
017A-2
203
024A-2
247
031A-2
348
046A-2
518
059A-2
762
075A-2
809
075A-2
830
088A-2
861
090A-2
114A-2
1268
Typical heat dissipa-
1)
tion
W
BTU/h
83
283
97
331
135
461
211
720
238
812
382
1303
486
1658
517
1764
667
2276
1)
tion
W
BTU/h
171
235
270
409
693
843
1187
1767
2600
2760
2835
2938
-
-
4327
Air flow
m 3 /h
CFM
43
25
43
25
43
25
43
25
179
105
179
105
179
105
179
105
179
105
Air flow
m 3 /h
CFM
43
25
43
25
43
25
43
25
43
25
101
59
101
59
179
105
179
105
288
170
159
94
139
82
159
94
139
82
Technical data 321
Noise
Frame size
dB(A)
59
R1
59
R1
59
R1
59
R1
64
R2
64
R2
76
R3
76
R3
76
R3
Noise
Frame size
dB(A)
59
R1
59
R1
59
R1
59
R1
59
R1
64
R2
64
R2
76
R3
76
R3
69
R4
70
R4 v2
63
R5
70
R4 v2
63
R5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs580-01 seriesAcs580-01-293a-4+j400

Table of Contents