Items To Be Observed In Programming; Positioning Instruction Activation Timing - Mitsubishi Electric FX3S Series User Manual

Hide thumbs Also See for FX3S Series:
Table of Contents

Advertisement

FX
/FX
/FX
3S
3G
3GC
Built-in Positioning Functions
4.7

Items To Be Observed in Programming

This section describes various programming items that will not be affected by any pulse output destination
devices (hardware).
For information on the pulse output destination devices (hardware) that are affected by programming items,
refer to the following sections.
4.7.1

Positioning Instruction Activation Timing

The following positioning instructions can be programmed as many times as needed. However, observe the
items shown in the following table to determine the instruction activation timing.
DSZR(FNC150)
DVIT(FNC151)
TBL(FNC152)
ABS(FNC155)
ZRN(FNC156)
PLSV(FNC157)
DRVI(FNC158)
DRVA(FNC159) Drive to Absolute
: If the pulse output destination device is now outputting pulses, the instruction cannot be activated. Refer
to the "Note" below.
: For the absolute position detection system, activate the ABS (FNC155) instruction after turning the
power ON for the servo amplifier. After executing this instruction, the current value will be read out from
the servo amplifier only once.
Turning this instruction OFF will turn the servo amplifier OFF.
Caution:
If the "pulse output monitor" (BUSY/READY) flag is on, and if a positioning instruction (excluding the ABS
instruction) or pulse output instruction (PLSR, PLSY) specifies the same pulse output destination device as
the one being used, the instruction cannot be executed.
Even after turning the instruction activation contact OFF, if the "pulse output monitor" (BUSY/READY) flag is
still on, do not execute a positioning instruction (including the PLSR and PLSY instructions) for an output with
the same output number.
Before activating such an instruction, check that the "pulse output monitor" (BUSY/READY) flag is off, and
then wait until 1 cycle or more of operation has been completed.
Pulse output destination device
*1.
Y002 is not available in FX
*2.
Y003 is available only when two high-speed output special adapters are connected to the FX
Downloaded from
ManualsNet.com
/FX
/FX
PLC User's Manual - Positioning Control Edition
3U
3UC
For use of the transistor output of the main unit, refer to Section 4.8.
For use of the high-speed output special adapter, refer to Section 4.9.
Description
Zero return instruction with
DOG search function
Interrupt Positioning
(interruption fixed-feed)
Positioning by batch setting
method
Current ABS value read-out
from servo amplifier
Zero return (without DOG
search function)
Variable speed Pulse Output
Drive to Increment
Y000
Y001
*1
Y002
*2
Y003
3G
search engine
For details on the each instructions, refer to Chapter 6 to 11.
DSZR DVIT
For examples of programs, refer to Chapter 12.
"Pulse output monitor" flag
M8340
M8350
M8360
M8370
PLC (14-point and 24-point type) and FX
4 Before Programming
4.7 Items To Be Observed in Programming
Instruction to be used
TBL
ABS
ZRN
PLSV DRVI DRVA
/FX
PLC.
3S
3GC
A
B
Apx.
PLC.
3U
B - 79