Terminal sizes

(frames R0...R8): 0.14...1.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes:
1)
Current [0(4)...20 mA, R
selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)...20 mA, R
selected with parameter 12.25AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output+24V (X2:10) = 6.0 W (250 mA / 24 V)
- User can use this source for either of theI/O connections (DI1... DI2- RO1 or DI3...DI6 -
EN
RO2~RO3).
HI
4)
The constant speed are set based on the combination of sources as follows:
Source defined by parameter
28.22
0
1
0
5)
The speed reference ramp is set based on the combination of sources as follows:
DI5
parameter 28.71
0
1
6)
Connected with jumpers at the factory.
7)
Applicable for R0~R2 frames only.
8)
Use shielded twisted-pair cables for digital signals.
9)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
10)
Input signal
11)
Output signal

Install optional modules, if any

The ACS560-01 drive supports the below option modules:
2
(all terminals)
< 500 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage[ 0(2)...10 V, R
in
Source defined by parameter
28.23
0
0
1
Ramp set
Acc/Dec time 1
Acc/Dec time 2
> 200 kohm] input as
in
> 200 kohm] input as
in
Constant speed active
Set speed through AI1
Constant frequency 1
Constant frequency 2
Parameters
Scalar control (default)
28.72 time 1
28.73 Freq deceleration time 1
28.74 time 2
28.75 time 2