112 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
1 - Starting OS time tick failed
2 - Creating system tasks failed
3 - Initializing file system failed
4 - Checking file system failed
EN
64B2
User set fault
HI
64B3
Macro parameteriza-
tion error
64E1
Kernel overload
6581
Parameter system
6591
Backup/Restore
timeout
65A1
FBA A parameter
conflict
6681
EFB communication
loss (Programmable
fault: 58.14 Commu-
nication loss action)
6682
EFB configuration file
6683
EFB invalid paramet-
erization
6684
EFB load fault
6685
EFB fault 2
6686
EFB fault 3
6882
Text 32-bit table
overflow
6885
Text file overflow
Cause
5 - Initializing WoRm volumes failed
6 - Loading FPGA configuration failed
7 - Loading application program failed
Loading user parameter set
failed.
Macro parameterization failed,
eg. Parameter default value that
cannot be changed has been at-
tempted to write.
Operating system error.
Note: This fault cannot be reset.
Parameter load or save failed.
During backup creating or
restoring operation a panel or
PC-tool has failed to communic-
ate with the drive as part of this
operation.
Requested functionality is not
activated.
Communication failed in embed-
ded fieldbus (EFB) communica-
tion.
Embedded fieldbus (EFB) config-
uration file could not be read.
Embedded fieldbus (EFB) para-
meter settings inconsistent or not
compatible with selected pro-
tocol.
Embedded fieldbus (EFB) pro-
tocol firmware could not be
loaded.
Version mismatch between EFB
protocol firmware and drive firm-
ware.
Fault reserved for the EFB pro-
tocol application.
Internal fault.
Internal fault.
The table size is too short for
opening language file.
What to do
Make sure a valid user parameter set exists.
Reload if uncertain.
Reboot the control unit using parameter
96.08 Control board boot or by cycling
power. If the problem persists, contact ABB.
Try forcing a save using parameter 96.07
Parameter save manually.
Check panel or PC-tool communication and
if it is still in backup or restore state.
Check PLC programming.
Check parameter groups 50 Fieldbus ad-
apter (FBA) and 51 FBA A settings.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the EIA-485/X5
terminals 29, 30 and 31 on the control unit.
Reload the firmware or replace the unit.
Contact ABB.
Check parameter group 58 Embedded
fieldbus.
Reload the firmware or replace the unit.
Contact ABB.
Check the documentation of the protocol.
Reset fault. If fault persists, contact ABB.
Reset the fault. If fault persists, contact ABB.