Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
5693
Measurement circuit
DFF
5695
Reduced run
5697
Charging feedback
5698
Unknown PU fault
50A0
Fan
6181
FPGA version incom-
patible
6306
FBA A mapping file
6481
Task overload
6487
Stack overflow
64A3
Application loading
8006
8007
8008
8009
800A
64A1
Internal file load
64A4
Rating ID fault
64A6
Adaptive program
64B1
Internal SSW fault
Cause
Measurement circuit fault.
Configured power units not
found.
Charging feedback signal miss-
ing.
The power unit logic generated
a fault which is not known by
software.
Cooling fan stuck or disconnec-
ted.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping file
read error.
Internal fault.
Note: This fault cannot be reset.
Internal fault.
Application file incompatible or
corrupted.
Not enough memory for the ap-
plication.
The application contains the
wrong system library version.
The application is empty.
The application contains invalid
tasks.
The application contains an un-
known target (system) library
function.
File read error.
Rating ID load error.
Fault in adaptive program.
A fatal error in the power-up
phase of System Software
(SSW).
Diagnostics 111
What to do
Contact ABB.
Configure the power units.
Check feedback signal from charging sys-
tem
Check the logic and software compatibility.
Check fan operation and connection.
Replace fan if faulty.
Reboot the control unit with parameter 96.08
Control board boot or by cycling power. If
the problem persists, contact ABB.
Contact ABB.
Reboot the control unit using parameter
96.08 Control board boot or by cycling
power. If the problem persists, contact ABB.
Reboot the control unit. If the problem per-
sists, contact ABB.
Check the auxiliary code. See actions for
each code below.
Reduce the size of the application. Reduce
the number of parameter mappings.
See the drive-specific log generated by
Automation Builder.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
In Automation Builder, give a "Clean" com-
mand and reload the application.
In Automation Builder, check application
task configuration, give a "Clean all" com-
mand, and reload the application.
Update the system library or reinstall Auto-
mation Builder.
See the drive-specific log generated by
Automation Builder.
Reboot the control unit. If the problem per-
sists, contact ABB.
Contact ABB.
Check the fault code extension.
SSW runs in partial functionality mode.
EN