Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
003
004
8009
Current limit
80A0
AI supervision
1 - AI1LessMIN
2 - AI1GreaterMAX
80B0
Signal supervision 1
80B1
Signal supervision 2
80B2
Signal supervision 3
80B3
Signal supervision 4
80B4
Signal supervision 5
80B5
Signal supervision 6
9081
External fault 1
9082
External fault 2
9083
External fault 3
9084
External fault 4
9085
External fault 5
A2A1
Current calibration
FA81
Safe torque off 1
FA82
Safe torque off 2
Cause
Overload occurred between
speed point 37.13 ULC speed
table point 3 and 37.14 ULC
speed table point 4.
Overload occurred between
speed point 37.14 ULC speed
table point 4 and 37.15 ULC
speed table point 5.
Motor actual current exceeded
the limit defined in parameter
30.17 Maximum current.
An analog signal is outside the
limits specified for the analog in-
put.
3 - AI2LessMIN
4 - AI2GreaterMAX
Fault generated by the signal
supervision function 1.
Fault generated by the signal
supervision function 2.
Fault generated by the signal
supervision function 3.
Fault generated by the signal
supervision function 4.
Fault generated by the signal
supervision function 5.
Fault generated by the signal
supervision function 6.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
Current offset and gain measure-
ment calibration will occur at next
start.
Safe torque off function is active,
ie. STO circuit 1 is broken.
Safe torque off function is active,
ie. STO circuit 2 is broken.
Diagnostics 115
What to do
Check the load.
Check the load.
Reduce the motor load. Check for any jam
or stall in motor. See parameter 30.17
Maximum current.
Check signal level, auxiliary code, wiring
connected to the input and the minim-
um/maximum limits of the input in parameter
group 12 Standard AI.
Check the source of the fault (parameter
32.07 Supervision 1 signal).
Check the source of the fault (parameter
32.17 Supervision 2 signal).
Check the source of the fault (parameter
32.27 Supervision 3 signal).
Check the source of the fault (parameter
32.37 Supervision 4 signal).
Check the source of the fault (parameter
32.47 Supervision 5 signal).
Check the source of the fault (parameter
32.57 Supervision 6 signal).
Check external device and parameter 31.01
External event 1 source.
Check external device and parameter 31.03
External event 2 source.
Check external device and parameter 31.05
External event 3 source.
Check external device and parameter 31.07
External event 4 source.
Check external device and parameter 31.09
External event 5 source.
Informative warning. (See parameter 99.13
ID run requested)
Check safety circuit connections and para-
meter 95.04 Control board supply.