116 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
FF61
ID run
EN
HI
1 - Maximum current limit too low
2 - Maximum speed limit or calculated field
weakening point too low
3 - Maximum torque limit too low
4 - Current measurement calibration not finished
within reasonable time
5...8 - Internal error
9 - (Asynchronous motors only). Acceleration
not finished within reasonable time.
A - (Asynchronous motors only) .Deceleration
not finished within reasonable time.
FF63
STO diagnostics fail-
ure.
FF81
FB A force trip
FF8E
EFB force trip
Cause
Motor ID run was not completed
successfully.
B - (Asynchronous motors only) Speed dropped
to zero during ID run.
C - (Permanent magnet motors only). First accel-
eration did not finish within reasonable time.
D - (Permanent magnet motors only). Second
acceleration did not finish within reasonable time.
E...10 - Internal error
11 - (Synchronous reluctance motors only). Pulse
test error.
12 - Motor too large for advanced standstill ID
run.
13 - (Asynchronous motors only). Motor data
error.
SW internal malfunction.
A fault trip command through
fieldbus adapter A.
A fault trip command through
embedded fieldbus interface.
What to do
Check
• nominal motor values in parameter group
98 User motor parameters.
• that no external control system is connec-
ted to the drive.
• that no operation limits prevent the com-
pletion of the ID run. Restore parameters
to default settings and try again.
• that the motor shaft is not locked.
• s
Cycle the power to the drive (and its control
unit, if powered separately).
Reboot the control unit (using parameter
96.08 Control board boot or by cycling
power.
Check the fault information provided by the
PLC.
Check the fault information provided by the
PLC.