114 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
7310
Overspeed
73B0
Emergency ramp
failed
73F0
Overfrequency
EN
00FA
HI
Other
7510
FBA A communica-
tion (Programmable
fault: 50.02 FBA A
comm loss func)
8001
ULC underload fault
001
002
003
004
8002
ULC overload fault
001
002
Cause
Motor is turning faster than
highest allowed speed.
Emergency stop did not finish
within expected time.
Maximum allowed output fre-
quency exceeded.
Motor is turning faster than the
highest allowed frequency due
to incorrectly set minimum/max-
imum frequency or the motor
rushes because of too high sup-
ply voltage or incorrect supply
voltage selection in parameter
95.01 Supply voltage.
-
Cyclical communication between
drive and fieldbus adapter mod-
ule A or between PLC and field-
bus adapter module A is lost.
User load curve: Signal has been
too long under the underload
curve.
Underload occurred between
speed point 37.11 ULC speed
table point 1 and 37.12 ULC
speed table point 2.
Underload occurred between
speed point 37.12 ULC speed
table point 2 and 37.13 ULC
speed table point 3.
Underload occurred between
speed point 37.13 ULC speed
table point 3 and 37.14 ULC
speed table point 4.
Underload occurred between
speed point 37.14 ULC speed
table point 4 and 37.15 ULC
speed table point 5.
User load curve: Signal has been
too long over the overload curve.
Overload occurred between
speed point 37.11 ULC speed
table point 1 and 37.12 ULC
speed table point 2.
Overload occurred between
speed point 37.12 ULC speed
table point 2 and 37.13 ULC
speed table point 3.
What to do
Check the minimum/maximum speed set-
tings, parameters 30.11 Minimum speed
and 30.12 Maximum speed, motor braking
torque, torque control, brake chopper and
resistor(s).
Check predefined ramp times (23.11...23.15
for mode Off1, 23.23 for mode Off3).
Check the auxiliary code.
Check minimum/maximum frequency set-
tings, parameters 30.13 Minimum frequency
and 30.14 Maximum frequency.
Check used supply voltage and voltage se-
lection parameter 95.01 Supply voltage.
Contact your local ABB representative,
quoting the auxiliary code.
Check the status of fieldbus communication.
Check parameter groups 50 Fieldbus ad-
apter (FBA), 51 FBA A settings, 52 FBA A
data in and 53 FBA A data out. Check cable
connections and communication of master.
See parameter 37.04 ULC underload ac-
tions.
Check the load.
Check the load.
Check the load.
Check the load.
See parameter 37.03 ULC overload actions.
Check the load.
Check the load.