5.1.5
Window screen display and switching
The window screen is displayed by writing the same No. as the window No. of the
screen to be displayed into the switching device used in overlap windows 1 to 5.
Two types of writing in the screen switching device are available: writing with the sequence program, and writing with the
GOT touch switch.
P
O
I NT
P
O
I
When "zero" is written in the screen switching device, the window screen is not displayed.
Example: When the switching device for base screen is D0, and that for overlap window 1 is D1.
Screen No. 15
Data 4
Data 4 999
Screen No. 15
Data 4
Screen No. 15
D
ata 4 999
Window Screen
No. 3
999
999
Sequence program example
X3
X4
MOV K3
X4
X3
MOV K0
The current values of the switching device are the
below because the GOT displays only base
screen No. 15.
D0 = "15"
D1 = "0"
Turn ON X3 with the sequence program, and D1
value is changed to three.
The GOT displays window screen No. 3 because
D1 value is changed to three.
When closing the window screen, operate either of
the following methods.
Window Screen
No. 3
• Touch
in the upper right corner of the window
screen.
• Write "zero" as the D1 value in the overlap
window1 screen switching device.
5. Drawing fundamentals
5.1 Switching the screen to be displayed
D1
D1
5 - 7
1
2
3
4
5
6